LPEXHZ Series – Instruction Sheet
LPEXHZ Series
Hazardous location LED exit sign
- Certified Class I Zone 2, Groups IIA, IIB and IIC
- Includes the addition of Class II Div. 1 and 2 Groups E, F, G and Class III
- Certified Class I Division 2, Groups A, B, C and D as per
- CSA C22.2 No.137-M1981
- Temperature code: T6 (maximum 85ºC as per Canadian
- Electrical Code, Part I and CSA C22.2 No.137-M1981)
- CSA certified, meets or exceeds CSA 22.2 No. 141 requirements
- Input voltages: 120 to 347VAC universal AC input; 6 to 48VDC universal DC input
- High impact thermoplastic frame, with built-in gasket to prevent water infiltration
- Suited for areas with the risk of presence of flammable gases, vapors or liquids able to create an explosive atmosphere
- Sealed faceplate of heavy-duty, vandal-resistant polycarbonate
- Tamper-resistant, hermetically sealed magnetic test switch
- Auto-diagnostic circuitry is standard on self-powered models
- Sealed, maintenance-free, nickel-cadmium batteries
- Batteries recharge as per CSA requirements and provide
- 90 minutes of emergency operation
- Long-life, energy-efficient ALINGAP red LED light source
- Energy efficient – consumes less than 3W in AC or DC mode
- Comes standard with industrial-grade, die-cast aluminum electrical box
- Suitable for cold weather: -20°C (-4°F) (self-powered model, “CW” option) and -40°C (-40°F) (AC only and AC-DC models)